Electrical safety
Multimeter measurement categories: CAT II, CAT III and CAT IV explained
The CAT rating on a meter describes the transient energy it can survive at a point in the installation, not just the voltage it can read. Here is how to choose correctly.
OSAKA TOOL Engineering Desk · · 2 min read
Why the category matters more than the voltage
Electrical installations carry transient overvoltages caused by switching and lightning. These impulses are largest near the supply origin and are attenuated by each layer of wiring and protection. IEC 61010-1 groups locations into measurement categories so that an instrument's insulation and protection can be matched to the energy available at that location.
The categories
- CAT II: circuits connected to the low-voltage installation by a plug, such as appliances and portable tools.
- CAT III: the fixed installation, including distribution boards, busbars, feeders, permanently connected motors and industrial equipment.
- CAT IV: the origin of the installation, including service drops, utility meters and primary overcurrent protection.
A rating always pairs a category with a voltage, for example CAT III 1000 V / CAT IV 600 V. A higher category at a given voltage indicates greater transient withstand.
Choosing in practice
- Electronics bench work on isolated, low-energy circuits: the category requirement is low, but good input protection still matters.
- Building electricians: CAT III 600 V as a minimum; CAT IV for service-entrance work.
- Industrial maintenance: CAT III 1000 V / CAT IV 600 V is a common professional specification.
The measurement chain
The system is only as safe as its lowest-rated component. Test leads, probe tips, clamps and adaptors must carry the same or a higher category and voltage rating. Use shrouded connectors and short exposed probe tips in CAT III and CAT IV environments, and inspect leads for damage before every use.