Electrical safety
Insulation resistance testing: test voltages, PI and DAR
A single megohm reading tells you little. Trend data, the polarisation index and correct test voltages tell you much more.
OSAKA TOOL Engineering Desk · · 2 min read
The test
An insulation tester applies a stabilised DC voltage between a conductor and earth, or between conductors, and measures the leakage current. It reports the result as resistance in megohms or gigohms.
Selecting the test voltage
Test voltages are chosen relative to the equipment's rated voltage. 250 V, 500 V and 1,000 V are common for low-voltage cables and equipment. Higher test voltages are used for medium-voltage assets. Follow the equipment manufacturer's and the applicable standard's guidance. Disconnect electronics that the test voltage could damage.
Time-based tests
- Dielectric absorption ratio (DAR): the 60-second reading divided by the 30-second reading.
- Polarisation index (PI): the 10-minute reading divided by the 1-minute reading.
Healthy, dry insulation shows rising resistance as absorption current decays. A ratio close to 1 suggests moisture or contamination.
Good practice
- Prove the circuit dead and isolate it before testing.
- Record temperature and humidity; resistance falls as temperature rises.
- Discharge the circuit after testing. Most testers do this automatically.
- Trend results over years rather than relying on a single pass or fail value.